1 January 2027 — automatic leak detection
40 CFR § 84.108 requires owners and operators of refrigerant-containing appliances used for industrial process refrigeration or commercial refrigeration with a full charge of 1,500 pounds or more of a refrigerant containing a regulated substance — or a substitute with a global warming potential (definition) above 53 — to install and use an automatic leak-detection system (definition). The timing depends on when the appliance was installed:
| Appliance installed | Leak detection required |
|---|---|
| On or after 1 January 2017, before 1 January 2026 | Installed and in use by 1 January 2027 |
| On or after 1 January 2026 | At installation, or within 30 days of it |
Appliance installed
On or after 1 January 2017, before 1 January 2026
Leak detection required
Installed and in use by 1 January 2027
Appliance installed
On or after 1 January 2026
Leak detection required
At installation, or within 30 days of it
If the appliance is older than that window, read § 84.108 directly rather than assuming the 2027 date covers it.
What the system has to do
- Direct-detection systems must monitor refrigerant concentrations in air near the compressor, evaporator, condenser and other leak-prone areas; detect a concentration of 10 ppm of the specific refrigerant; and alert at 100 ppm (§ 84.108(f)).
- Condition-monitoring systems must alert when measurements indicate a loss of 50 pounds of refrigerant, or 10 per cent of the full charge — whichever is less (§ 84.108(g)).
- Systems must be audited and calibrated annually (§ 84.108(d)) and must monitor components inside an enclosed building or structure (§ 84.108(e)).
When an alert fires
The owner or operator must calculate the leak rate within 30 days of the alert (120 days where an industrial process shutdown is necessary) — or preemptively repair the leak and then calculate it — and, if the leak rate is above the applicable threshold, follow the full leak-repair requirements in § 84.106 (§ 84.108(h)).
Records to keep
§ 84.108(i) requires records for at least three years of: the leak-detection system installation, each annual audit and calibration, every date the system triggered an alert, and the location of the leak(s) behind each alarm.