F-Gas leak-check intervals & exemptions

The interval depends on the system's charge in tonnes of CO₂ equivalent — not the refrigerant weight in kilograms — and it applies to each system on its own, never to a fleet total. This is the table in EU F-Gas Regulation (EU) 2024/573, with the exemptions that can take equipment out of the schedule entirely.

Updated 5 November 20265 min readReviewed against the published regulation

In one sentence: How often a system needs a leak check depends on its charge in tonnes of CO₂ equivalent, calculated per system — never on a fleet total.

Manifold gauges connected to a refrigeration unit

The leak-check table

Below 5 tCO₂e
Minimum check interval
No mandatory check
With automatic leak detection
—
5 to <50 tCO₂e
Minimum check interval
Every 12 months
With automatic leak detection
Every 24 months
50 to <500 tCO₂e
Minimum check interval
Every 6 months
With automatic leak detection
Every 12 months
500 tCO₂e or more
Minimum check interval
Every 3 months
With automatic leak detection
Every 6 months — and an automatic leak-detection system is mandatory

Systems of 500 tCO₂e or more must also carry a permanent automatic leak-detection system. Where a leak is found and repaired, the system must be re-checked within one month to confirm the repair held.

Hermetically sealed, labelled equipment below 10 tCO₂e is exempt from these intervals. From 10 tCO₂e it follows the same rows as any other system — the exemption raises the entry threshold, it does not remove the obligation.

Exemptions

  • Below 5 tCO₂e. No mandatory leak check — many smaller units on lower-GWP refrigerants fall under the line.
  • Hermetically sealed, labelled equipment — below 10 tCO₂e only. The regulation exempts equipment whose refrigerant joints are welded or brazed tight at manufacture (tested leakage rate under 3 g/year) and marked as hermetically sealed. The exemption lifts the entry threshold from 5 to 10 tCO₂e, and no further: at 10 tCO₂e or more the standard table applies again — 12 months at 10–<50 tCO₂e, 6 months at 50–<500 tCO₂e, and 3 months plus a mandatory permanent leak-detection system at 500 tCO₂e or more.

Calculating the tCO₂e

tCO₂e = charge (kg) × GWP ÷ 1,000

AR4 vs AR5: what is the difference?
GWP values are published in generations: AR4 is the IPCC Fourth Assessment Report, AR5 is the Fifth. For some HFCs the AR5 value is around 8–10% lower, so the same charge can produce a different tCO₂e — always state which basis a report uses.

What is GWP?

Records

For every system that requires checks, keep the type and quantity of refrigerant, anything added or recovered, the results of each leak check, and the identity of the engineer and company that carried it out. Records must be retained for at least five years and produced to the regulator on request.

How Cryovo produces this

Cryovo carries an AR5 GWP table with the basis stated on every report, computes each system's tCO₂e from its real charge, applies the interval to each system individually, and flags units that need a permanent leak-detection system — so the schedule and the evidence come out of the same record.

Start free — no card

General information, not legal advice — always check the current regulation and manufacturer instructions for your equipment and jurisdiction. New to the vocabulary? See the Help page and the glossary.

Terms used in this guide

  • tCO₂e— Tonnes of CO₂-equivalent: refrigerant charge × GWP ÷ 1,000.
  • GWP— Global Warming Potential — how much a gas warms compared with CO₂ over 100 years.
  • Leak check— The inspection interval required for a system, based on its tCO₂e.
  • Automatic leak detection (ALD)— A system that continuously watches for refrigerant leaks.